explosion proof air conditioning







UNIT DIMENSIONS (INCHES)
| UNIT MODEL |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
L |
| BTB30VDXRM | 32 | 84 | 31 | 28 | 47 | 31 1/2 | 83 1/2 | 2 | 47 1/2 | 31 1/2 | 28 1/2 |
| BTB36VDXRM | 32 | 84 | 31 | 28 | 47 | 31 1/2 | 83 1/2 | 2 | 47 1/2 | 31 1/2 | 28 1/2 |
| BTB42VDXRM | 32 | 84 | 31 | 28 | 47 | 31 1/2 | 83 1/2 | 2 | 47 1/2 | 31 1/2 | 28 1/2 |
| BTB48VDXRM | 32 | 84 | 31 | 28 | 47 | 31 1/2 | 83 1/2 | 2 | 47 1/2 | 31 1/2 | 28 1/2 |
| BTB60VDXRM | P | e | n | d | i | n | g | I | n | f | o |
| BTB72VDXRM | 47 | 94 | 36 | 43 | 52 5/8 | 46 1/2 | 93 1/2 | 2 | 53 1/8 | 35 7/8 | 43 1/2 |
| BTB90VDXRM | 47 | 94 | 36 | 43 | 52 5/8 | 46 1/2 | 93 1/2 | 2 | 53 1/8 | 35 7/8 | 43 1/2 |
| BTB120VDXRM | 47 | 94 | 36 | 43 | 52 5/8 | 46 1/2 | 93 1/2 | 2 | 53 1/8 | 35 7/8 | 43 1/2 |
Physical Data
| UNIT MODEL NO. | BTB30VDXRM | BTB36VDXRM | BTB42VDXRM | BTB48VDXRM |
| OPERATING WEIGHT (lbs.) (APPROX) |
585 |
595 |
975 |
980 |
| NOMINAL CAPACITIES
Cooling (B.T.U.H.)@ 60HZ. Heating K.W. (opt.) Air Flow (C.F.M.) |
- 30,000 6/12 1200 |
- 36,000 6/12 1200 |
- 42,000 6/12 1600 |
- 48,000 6/12 1600 |
| VOLTAGE AVAILABLE
1 or 3 Phase 50 or 60 Hz. |
- 208/230 460 |
- 208/230 460 |
- 208/230 460 |
- 208/230 460 |
| COMPRESSOR(S)
Amps. @ 208/230V/ 1/3 Ph Amps 460 V. 3ph |
- 15.0/10.7 5.0 |
- 17.9/11.4 5.7 |
- 20.4/13.9 7.1 |
- 28.0/19.3 7.5 |
| CONDENSER SECTION
Coil Face Area (sq. in.) Rows/Fins per inch Motor H.P. (r.p.m.) |
- 572 4/12 1/2 (1200) |
- 572 4/12 1/2 (1200) |
- 572 6/12 1 (1800) |
- 572 6/12 1 (1800) |
| EVAPORATOR SECTION
Coil Face Area (sq. in.) Rows/Fins per inch Motor H.P. (Qty) |
- 440 3/12 2 (1) |
- 440 3/12 2 (1) |
- 440 4/12 2 (1) |
- 440 4/12 2 (1) |
| REFRIGERANT |
R-22 |
R-22 |
R-22 |
R-22 |
| FILTER - Type: PLEATED 30% EFFICIENT
(Nominal Size) - Size (Number) |
- 25x20x4 (1) |
- 25x20x4 (1) |
- 25x20x4 (1) |
- 25x20x4 (1) |
(Pysical Data continued)
| UNIT MODEL NO. | BTB60VDXRM | BTB72VDXRM | BTB90VDXRM | BTB120VDXRM |
| OPERATING WEIGHT (lbs.) (APPROX) |
995 |
1065 |
1140 |
1180 |
| NOMINAL CAPACITIES
Cooling (B.T.U.H.)@ 60HZ. Heating K.W. (opt.) Air Flow (C.F.M.) |
- 60,000 6/12 2000 |
- 72,000 6/12/18/24 2400 |
- 90,00 6/12/18/24 3000 |
- 120,000 6/12/18/24 4000 |
| VOLTAGE AVAILABLE
1 or 3 Phase 50 or 60 Hz. |
- 208/230 460 |
- 208/230 460 |
- 208/230 460 |
- 208/230 460 |
| COMPRESSOR(S)
Amps. @ 208/230V/ 1/3 Ph Amps 460 V. 3ph |
- 32.1/19.3 10.0 |
- 27.9/20.7 10.0 |
- N/A /32.1 16.4 |
- N/A /42.0 19.2 |
| CONDENSER SECTION
Coil Face Area (sq. in.) Rows/Fins per inch Motor H.P. (r.p.m.) |
- 870 4/12 1 (1800) |
- 1088 4/12 1-1/2 (1800) |
- 1088 4/12 1-1/2 (1800) |
- 1088 6/9 2 (1800) |
| EVAPORATOR SECTION
Coil Face Area (sq. in.) Rows/Fins per inch Motor H.P. (Qty) |
- 560 4/12 2 (1) |
- 780 4/12 2 (1) |
- 780 5/12 2 (2) |
- 780 5/12 2 (2) |
| REFRIGERANT |
R-22 |
R-22 |
R-22 |
R-22 |
| FILTER - Type: PLEATED 30% EFFICIENT
(Nominal Size) - Size (Number) |
Pending Info |
- 25x20x4 (2) |
- 25x20x4 (2) |
- 25x20x4 (2) |
Note: Capacities based on standard ARI conditions (80/67 EAT, 95F AMB)
Standard Specifications Guideline
Furnish and install a packaged, totally self contained, explosion proof (general purpose optional) cab mount air conditioner is ETL certified by Intertek Testing Services to be in compliance with applicable UL and CSA codes and standards for Class I or II, Divisions I or II hazardous locations. The unit shall include variable damper pressurization to meet NFPA 496 code requirements. The unit shall also include an *explosion proof full hermetic compressor. The evaporator and condenser fan motors shall be *explosion proof. High voltage electrical controls shall be in one NEMA 7 *explosion proof control box. Low voltage electrical controls shall be served by an intrinsically safe relay. Unit options shall include *explosion proof electric heat and Heresite baked phenolic or epoxy coil coatings for corrosion protection.
The entire unit shall be constructed of 16 gauge type 304 (type 316 optional) stainless steel for maximum protection from corrosive environments. The evaporator and condenser coils shall have copper tubes and aluminum fins. The evaporator section shall be insulated with 1" thick 1 1/2 lbs. density acoustic insulation. The compressor shall be mounted on external vibration isolators for quiet operation. The compressor shall be high efficiency full hermetic type with internal pressure relief valves. A pre-trapped condensate drain connection shall be provided.
The unit controls shall include a thermostatically controlled expansion valve, high and low refrigerant pressure cut-out switches, solid state time delay relay to prevent short cycling and frost control to stop compressor in the event of coil icing due to dirty filter, etc. The unit shall be fully serviceable from side access doors and external grilles. Service doors shall be double wall, internally insulated. Provide service valves for pump-down capability. The unit shall be equipped with refrigerant sight glass with moisture indicator for aid in servicing system.
The system shall be a model BTB__VDX__C__-RM as manufactured by The Birdwell Company in Houston, Texas (no equal). Manufacturer reserves the right to change any product specifications without notice.
*(Div. 1 units)